IPS-ATDW1202300 276KW 50V 100V 120V 1000A 2000A 2300A High-Power Parallel Power Supply System Multi-Unit High-Power Rectifier
① Model:IPS-ATDW1202300 ② AC INPUT: 3-Phase 600V AC ±10% 50/60Hz ③ Output Voltage: 0-120VDC ④ Max Output Current: 0-2300A ⑤ MAX POWER: 276KW ⑥ Size: 900×630×1200(MM) ⑦ NW/GW: 620KG/700KG ⑧ Shell: Iron Casing ⑨ Communication: RS485 (Modbus-RTU) Wechat Number/Whatsapp ID: +86-18928830209 Email: info@idealplusing.com Office telephone number: +86-20-89282095
Datasheet: Preview



AC Input

3-Phase 600V AC ±10% 50/60Hz

Model

IPS-ATDW1202300

Output Voltage

0-120VDC

Output Current

0-2300A

Output Power

276KW

Protection Functions

Multiple protection functions, including overvoltage, overcurrent, undervoltage, short circuit, phase loss, and overheating.

Control Method

PLC Analog Control Isolation Module

Control Method

RS485 Serial Port / TCP Network Port Control Function

Display & Operation

7‑inch color touchscreen with real‑time V/I monitoring.

Operation: Touch + Local/Remote control.

Communication

RS‑485 (Modbus‑RTU) + CANSupports remote read/write of all major parameters.

Cooling

Water Cooling

Dimensions (HWL)

900 * 630 * 1200 mm

Weight

Net: 620 KG / Gross: 700 KG

Environment

Op: ‑20℃~45℃, 10%~95% RHSt: ‑20℃~70℃, 10%~95% RH

Notes

1. Product Structure: Composed of a primary rectification unit, an inverter unit (IGBT), a high-frequency transformer, a secondary rectification system, a drive and control system, a protection system, a communication system, a cooling system, and other components.
2. Application Fields: Wastewater treatment, electroplating, electrolysis, electrochemistry, electrophoretic painting, oxidation, rare earth smelting, testing, and other application areas.
3. Parallel Operation Architecture: Utilizing CAN communication, the current of the slave unit is synchronized with that of the master unit. The chassis is designed with reserved space to accommodate future expansion, allowing for an increase in maximum current capacity through the subsequent addition of modules. For every 18 kW increase in output power, one 300A/1700V IGBT is added; for every 36 kW increase, one 300A rectifier bridge is added; for every 12 kW increase, one magnetic core is added; and for every 100A increase in output current, one diode is added.


Design Operating Conditions
1Ambient Temperature: -20°C to 45°C
2Relative Humidity: 10%–95%
3Altitude: ≤ 1500 m
4Vertical Tilt: ≤5°
5The equipment is installed indoors.
6No severe vibration or shock.
7The air must be free from excessive dust and explosive gases, and the environment must be free from highly corrosive gases.
Features
1Product Structure: Composed of a primary rectification unit, an inverter unit (IGBT), a high-frequency transformer, a secondary rectification system, a drive and control system, a protection system, a communication system, a cooling system, and other components.
2Application Fields: Wastewater treatment, electroplating, electrolysis, electrochemistry, electrophoretic painting, oxidation, rare earth smelting, testing, and other application areas.
3Parallel Operation Architecture: Utilizing CAN communication, the current of the slave unit is synchronized with that of the master unit. The chassis is designed with reserved space to accommodate future expansion, allowing for an increase in maximum current capacity through the subsequent addition of modules. For every 18 kW increase in output power, one 300A/1700V IGBT is added; for every 36 kW increase, one 300A rectifier bridge is added; for every 12 kW increase, one magnetic core is added; and for every 100A increase in output current, one diode is added.
Control Method
1. Local Unit Remote Control Box FunctionsVoltage and Current Display
Constant Voltage/Constant Current Mode Switching
Timer/Amp-Hour Meter – Alarm
Voltage/Current-Time Parameter Settings
Power Status Display
RS485 Serial Port / TCP Network Port Control FunctionVoltage and Current Display
Power Status Display
Voltage/Current Settings
Constant Voltage/Constant Current Mode Switching
Power On/Off Control
Local Touchscreen Control FunctionCustomizable according to client requirements.
PLC Analog Control Isolation Module0-5V/4-20mA