Product Categories

IPS-LNBI400-100KST 100KW 350~750VDC Anti-Theft Mounting Structure Fiber Optic Synchronization Interface Backplane Bus Architecture
①Model:IPS-LNBI400-100KST ② AC INPUT: 3-phase 3-wire / 3-phase 4-wire 220/380VAC±15% 50/60HZ or Customize (Other voltages available upon request; please contact technical support for details) ③ DC OUTPUT:350~750VDC ④ Maximum equipment power:110KW ; Rated equipment power: 100KW ⑤ Application: Peak shaving/valley filling, PV energy storage DC integration, industrial/commercial energy storage, peak-valley arbitrage (or customized) ⑥ Adjusting method: Color touchscreen (Chinese/English switchable), integrated display & control ⑦ Adjustable output power factor (-0.8 leading ~ 1.0 ~ +0.8 lagging), customizable reactive power compensation ⑧ Protection features: DC reverse connection, over/under voltage, over-current, overheating protection; insulation & temperature monitoring ⑨ Core Design: 3-phase energy storage system, 50/60HZ grid adaptive, DC-AC bidirectional conversion, four-quadrant SVPWM/SPWM, PF>0.99 ⑩ Additional: Recommended rated voltage 384/420/480VDC; pre-charging mode (resistor + DC-DC)
Datasheet: Download

Technical parameters and selection criteria

High-frequency equipment parameters

Rated equipment power

50KW

100KW

200KW

500KW

1000KW

Maximum equipment power

55KW

110KW

220KW

550KW

1100KW

DC side parameters

DC voltage range

600-900VDC

Voltage/current regulation accuracy

±1%FS

DC current ripple

<3%Irms

DC side parameters

AC wiring method

3-phase 3-wire /3-phase 4-wire (Please specify when ordering)

Rated grid voltage

220/380Vac (Other voltages available upon request; please contact technical support for details)

Power grid voltage range

±15%

Rated grid frequency

50/60Hz

Power grid frequency range

10%

Total current distortion rate

THD < 3% (standard power grid)

Power factor

-0.8 leading ~ 1.0 ~ +0.8 lagging, adjustable

Independent inverter mode

Output voltage

220/380VAC

Output voltage regulation accuracy

±1%

Output voltage distortion

<3% (resistive load)

Output frequency

50/60Hz

Output frequency stability

±1%

Three-phase load unbalance

100%

System Parameters

Operating modes

Manual mode, Automatic mode, EMS mode

Charging and discharging modes

Constant current Constant voltage, Constant power Constant voltage

Pre-charging mode

Resistor pre-charging

Maximum conversion efficiency

98%

Noise

<65dB

Protection level

IP20 (customizable to IP54)

Permissible ambient temperature

-15to 50(Other temperatures can be customized)

Permissible relative temperature

0-95% (no condensation)

Permitted altitude

6000m; for altitudes exceeding 2000 meters, derating is required (1% derating for every 100 meters increase in altitude).

Cooling method

Intelligent air cooling

Emergency shutdown

There is an emergency stop button.

Display

Touchscreen

Insulation monitoring

Insulation tester

Temperature monitoring

Temperature monitoring instrument

Communication interface

RS48 , Ethemet , WIFI , GPRS , CAN

Communication protocol

Modbus RTU/ Modbus TCP

This indicates optional features. The above technical parameters are standard parameters and are for reference only; they can be customized according to the user's actual needs.

 

Power frequency equipment parameters

Rated equipment power

50KW

100KW

200KW

500KW

1000KW

Maximum equipment power

55KW

110KW

220KW

550KW

1100KW

DC side parameters

DC voltage range

350-750VDC

350-750VDC

350-750VDC

400-850VDC

500-850VDC

Recommended rated voltage

384/420/480

420/480

480

600

600

Voltage/current regulation accuracy

±1%FS

DC current ripple

<3%Irms

DC side parameters

AC wiring method

3-phase 3-wire / 3-phase four-wire (Please specify when ordering)

Rated grid voltage

220/380/630VAC (Other voltages are available upon request)

Power grid voltage range

±15%

Rated grid frequency

50/60HZ

Power grid frequency range

±10%

Total current distortion rate

THD < 3% (standard power grid)

Power factor

-0.8 leading ~ 1.0 ~ +0.8 lagging, adjustable

Independent inverter mode

Output voltage

220380/630VAC (other voltages can be customized) +1%

Output voltage distortion

<3% (resistive load)

Output frequency

50/60HZ±1%

Three-phase load unbalance

100%

System Parameters

Operating modes

Manual mode, Automatic mode, EMS mode

Charging and discharging modes

Constant current → Constant voltage, Constant power → Constant voltage

Pre-charging mode

Resistor pre-charging, DC-DC pre-charging

Maximum conversion efficiency

96% (including transformers)

Noise

<65dB

Protection level

IP20 (customizable to IP54)

Permissible ambient temperature

-15℃ to 50℃ (Other temperatures can be customized)

Permissible relative temperature

0-95% (no condensation)

Permitted altitude

≤6000m; for altitudes exceeding 2000 meters, derating is required (1% derating for every 100 meters increase in altitude).

Cooling method

Intelligent air cooling

Emergency shutdown

There is an emergency stop button.

Display

Touchscreen

Insulation monitoring

Insulation tester

Temperature monitoring

Temperature monitoring instrument

Communication interface

RS48 , Ethemet , WIFI , GPRS , CAN

Communication protocol

Modbus RTU/ Modbus TCP

This indicates optional features. The above technical parameters are standard parameters and are for reference only; they can be customized according to the user's actual needs.


WhatsApp
Wechat
Contact Us
Your Name:
Your Email:
Your Message:
This website uses cookies to enhance user experience and to analyze performance and traffic on our website.
We also share information about your use of our site with our social media, advertising and analytics partners.
Do Not Sell My Personal Information
Accept Cookies